Conext XW Pro Installation Guide

Conext Gateway Installation
The Conext XW Pro can be controlled remotely by connecting a Conext Gateway.
The Conext Gateway allows access to programming features of the Conext XW Pro and
allows the system to be modified to specific installation requirements.
The Conext Gateway can be connected to the Conext XW Pro via the Xanbus network.
Installing the Conext Gateway via the Xanbus Network
WARNING
IGNITION AND FIRE HAZARD
n This equipment is not ignition protected. To prevent fire or explosion, do not install this
product in locations that require ignition-protected equipment. This includes any
confined space containing vented batteries, or flammable chemicals such as, natural
gas (NG), liquid petroleum gas (LPG) or gasoline (Benzine/Petrol).
n Do not install in a confined space with machinery powered by flammable chemicals, or
storage tanks, fittings, or other connections between components of fuel or flammable
chemical systems.
n Do not install the inverter near readily flammable materials such as cloth, paper, straw,
or plastic sheeting. Keep flammable materials a minimum distance of 600 cm (24 in.)
from the top surface and 30 cm (12 in.) from either side surface and the front of the
Conext XW Pro Inverter/Charger.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The Conext Gateway is connected to the Xanbus network via either of the two Xanbus
network ports located at the bottom of the Conext XW Pro chassis (as shown in Figure
63 ).
Figure 63 Xanbus Port Locations
For more information about installing a Xanbus-enabled device as part of a network
system, see "The Xanbus Network" on page99.
For wall-mounting and other installation instructions, see the Conext Gateway Owner's
Guide (975-0806-01-01).
Conext XW Pro Installation Guide Access Installation
107 This manual is intended for use by qualified personnel 990-91228A-01