Conext XW Pro Installation Guide

Note: To complete the conversion, you must refer to firmware upgrade instructions in
the Conext Gateway Owner's Guide (975-0806-01-01) available from
http://solar.schneider-electric.com.
Note: To set up a three-phase system using three 120V-configured Conext XW Pro
units, perform the conversion procedure for all three Conext XW Pros.
Installation Tools and Materials
To complete the conversion, you will need the following:
n a Phillips #2 screwdriver
n one small jumper and three large jumpers, included with the Conext XW Pro, see
Figure 69 .
Figure 69 Conext XW Pro Jumpers
Disconnecting Power Sources
To disconnect power sources:
1. Put the Conext XW Pro system in Standby mode (for more information about standby
mode, see the Owner’s Guide), disconnect AC sources (such as the utility grid and
generators) by turning off the AC input breakers, and disconnect DC sources (for
example, batteries) by turning off the DCbreaker.
2. Turn off and disconnect all AC loads by turning off the AC output breaker.
Converting Split-phase to Single-phase Conext XW Pro Installation Guide
990-91228A-01 This manual is intended for use by qualified personnel 124