Conext XW Pro Installation Guide
Reconfiguring the Secondary Transformer Wires on X1 and X2 Connectors
To reconfigure the secondary transformer wires on the X1 and X2 connectors:
1. Locate the X1 and X2 connectors (shown below).
Figure 71 Connector Locations
2. Remove the secondary transformer wire X2 (black) from slot X2-A, and then insert it
into slot X2-B, see Figure 72 and Figure 73 .
3. Remove the secondary transformer wire X3 (white) from slot X3-A, and then insert it
into slot X3-B, see Figure 72 and Figure 73 .
4. Insert one small jumper between slot X2-A and X2-B, see Figure 72 and Figure 73 .
Insert jumper on top of the wire.
5. Tighten all terminals to 35 in-lb (4.0 N-m) per the torque information printed on the
ACboard. See Figure 71 for the torque information location.
Conext XW Pro Installation Guide Converting Split-phase to Single-phase