Conext XW Pro Installation Guide
Reconfiguring the AC Ports on the Load, AC1, and AC2 Connectors
To reconfigure the AC ports on the Load, AC1 (Grid), and AC2 (Gen) connectors:
1. Locate the Load, AC1 (Grid), and AC2 (Gen) connectors, see Figure 74 .
2. Insert one large jumper in each connector to short out N and L2.
Figure 74 Jumper Locations and AC Cable Configuration on AC Ports
3. Connect the AC cables as shown in Figure 74 . Insert jumper on top of the wire.
4. Tighten all terminals per the torque information printed on the AC board. SeeFigure
71 on page 127 for the torque information location.
5. Reconnect the DC sources (for example, batteries) by turning on the DCbreaker.
Conext XW Pro Installation Guide Converting Split-phase to Single-phase
129 This manual is intended for use by qualified personnel 990-91228A-01