Conext XW Pro Installation Guide

Torque Values
Torque Values for the Conext XW Pro
Wire Size Torque Value
AWG mm
2
In-lb N-m
1410 1.632.59 35 4.0
8 3.26 40 4.5
6–4 4.115.19 45 5.1
Table 4Torque Values for AC Wiring (AC Terminals and Ground Bar)
Wire Size Torque Value
AWG mm
2
In-lbs N-m
6–4 4.115.19 45 5.1
3–2 5.836.54 50 5.6
Table 5Torque Values for the Chassis Ground Lug
Torque Value
Ft-lbs N-m
15 20.4
Table 6Torque Values for the Inverter
Battery Terminals
Torque Values for the Power Distribution Panel (PDP)
Wire Size Torque Value
AWG mm
2
In-lb N-m
1610 1.292.59 45 5.1
8 3.26 45 5.1
6–4 4.115.19 45 5.1
Table 7Torque Values for AC Disconnects and AC Breakers
Wire Size Torque Value
AWG mm
2
In-lbs N-m
1410 1.632.59 35 4.0
8 3.26 40 4.5
6–4 4.115.19 45 5.1
3–2/0 5.839.27 50 5.6
Table 8Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus,
and DC Positive Bus in the PDP
Pre-Installation Planning Conext XW Pro Installation Guide
990-91228A-01 This manual is intended for use by qualified personnel 40