Conext XW Pro Installation Guide

WARNING
LACK OF GROUND FAULT DETECTION HAZARD
Ground fault detection on the MPPT 60 150 solar charge controller is circumvented when
the Conext XW Pro battery negative circuit is grounded.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Note: If a grounded DC system is required, ensure that the system bonding is done in
one location only, and that all conductors and connections comply with all applicable
NEC and local installation codes.
Figure 25 DC Grounding Using a Power Distribution Panel (PDP)
Installing the Battery Temperature Sensor
WARNING
BATTERY TEMPERATURE
n Battery temperature sensing provides necessary information for performance and
safety.
n Always install and connect the Battery Temperature Sensor (BTS). Always install and
connect the Battery Temperature Sensor (BTS) if an external BMS fulfilling this function
is not used. See the note directly below.
n Ensure any external BMS and battery used is compatible with the Conext system.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Conext XW Pro Installation Guide Wiring
51 This manual is intended for use by qualified personnel 990-91228A-01