Conext XW Pro Installation Guide

To connect the Power Distribution Panel (PDP) to the Conext XW Pro:
1. Connect the positive battery cable (pre-installed in the PDP) to the positive battery
terminal at the bottom of the Conext XW Pro, as shown in Figure 27 .
2. Connect the negative battery cable (pre-installed in the PDP) to the negative battery
terminal at the bottom of the Conext XW Pro.
Note: When making the connections, be sure to observe correct hardware stacking
and proper polarity, and ensure that nothing obstructs the connection between the
terminal surface and the battery cable lug, see Figure 28 .
Figure 28 Battery Cable Connection
3. Attach the DC terminal covers (included with the Conext XW Pro) to the bottom of
the Conext XW Pro DC terminals.
To connect the PDP to the Battery Bank:
Connect your battery cables (not included) to the PDP. Connect the negative battery
cable to the DC Negative Bus, and the positive battery cable to the input end of the
GJ250A 160 VDC, 3/8" stud DC breaker (pre-installed in the PDP), as shown in Figure
29.
Note: Toproperly attach and torque the positive cable to the DC breaker, you may
need to temporarily remove the breaker from the rail.
Route your battery cables from the PDP, through your preferred conduit path, to the
battery location. Do not connect the cables to the battery yet.
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in "Making AC Connections" on page57.
Conext XW Pro Installation Guide Wiring
55 This manual is intended for use by qualified personnel 990-91228A-01