Conext XW Pro Installation Guide

Figure 39 Transition to Disabled Mode
2. Monitor the invert (green kW) LED to confirm which mode the inverter is in:
a. kW LED OFF Invert mode is disabled. The inverter/charger is not powering
the AC loads. However, if good AC is present, it is passed through to the
loads.
b. Sch displayed on the inverter information panel The inverter/charger is in
searchmode and is looking for an AC load greater than the Maximum Search
Watts setting (default=25watts). The display shows Sch (Search) when this
mode has been enabled.
c. LED ON The inverter/charger is on. The inverter is operating and is able to
provide power to the AC loads. This is the default mode on initial power-up
once the unit is taken out of standby mode.
If the inverter is not operating or the inverter LED (kW) does not turn on, check all
connections. Check the inverter’s DC voltage and polarity on the positive (+) and
negative(–) terminals. Check the Event LED. If the Event LED is on, check for an event
code on the information panel. Correct the reported event and clear the event by
acknowledging it. If the DC voltage is low, then the battery bank needs to be charged
externally. Charge the battery bank and restart the functional test.
Conext XW Pro Installation Guide Wiring