XW PRO Li-ion Battery Solution Guide

Manufacturer Model
Nominal
Rating
Protocol
DC
Coupling
1
AC
Coupling
Start-Up Sequence
Recommended Number of
Batteries in Parallel
Single XW Pro
Pylontech US3000 3.55 kWh CAN See note 1 YES
With DC disconnect open, start batteries in sequence.
Then close DC disconnect.
4
Pylontech
Force L1
(x3)
10.65 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L1
(x4)
14.2 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L1
(x5)
17.76 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L1
(x6)
21.31 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L1
(x7)
24.86 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L2
(x3)
10.65 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
Pylontech
Force L2
(x4)
14.2 kWh CAN See note 1 YES Close DC disconnect on the inverter, then start batteries. 2
NOTICE
RISK OF DAMAGE TO THE BATTERY AND BATTERY INVERTER
Always follow the recommended settings, which are intended to operate the batteries within their recommended ranges and minimize
BMS tripping. Consult the battery manufacturer if adjustments are required.
Failure to follow these instructions can result in equipment damage.
1
Schneider Electric MPPT charge controllers integration with the BMS is planned in a future release. If connected with manual (static)
charge settings, it is recommended to configure a charge block on the XW Pro during daylight hours when the battery may be charging
from the MPPT charge controllers.
XW Pro Li-ion Battery Solution Guide
990-6359A This manual is intended for use by qualified personnel 12