XW PRO Li-ion Battery Solution Guide

connections are done, power on Conext Gateway and BMS. Refer to the Conext Gateway
Owners Guide (Part Number: 975-0806-01-03) for more details on installation.
NOTICE
RISK OF BMS OR CONEXT GATEWAY DAMAGE
BMS and Conext Gateway must be powered off while doing the connections.
Failure to follow these instructions can result in equipment damage.
Port Signal Pin Number
RS485 Port 1
ISO2 RS485 1A 18
ISO2 RS485 1B 20
ISO2 RS485 GND 16
RS485 Port 2
ISO2 RS485 2A 24
ISO2 RS485 2B 26
ISO2 RS485 GND 22
CAN Port 1
ISO1 CANL 12
ISO1 CANH 14
ISO1 CAN GND 10
NOTICE
RISK OF BATTERY DAMAGE
Consult the battery manufacturer's information for wiring connection details for use with a BMS.
Failure to follow these instructions can result in equipment damage.
Conext Gateway BMS Communication Setup
Only the master BMS in the system, once discovered, must be associated with the XW Pro
inverter to which its battery packs are connected. The association is completed as
described in BMS Association on page 8.
990-6359A This manual is intended for use by qualified personnel 6
XW Pro Li-ion Battery Solution Guide