Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Specifications
A–2 975-0714-01-01
This manual is for use by qualified personnel only
Electrical Specifications
Tab le A-1 Conext XW+ Electrical Specifications
Conext XW+
8548
Conext XW+
7048
Continuous Output Power 6,800 W 5,500 W
Surge Rating (Overload for 1 minute) 12,000 W 9,500 W
Surge Rating (Overload for 5 minutes) 11,000 W 9,000 W
Surge Rating (Overload for 30 minutes) 8,500 W 7,000 W
Surge Current 53 A
rms
(60 s) 40 A
rms
(60 s)
Waveform True Sine Wave
Idle Consumption—invert mode, no load 28 W 26 W
Idle Consumption—search mode < 7 W
AC Output Voltage 230 Vac ±3%
AC Input Voltage Range (Bypass/Charge Mode) 165–280 V
AC Input Breaker 60 A double-pole
AC Input Frequency Range (Bypass/Charge
Mode)
45–55 Hz (default)
40–68 Hz (allowable)
AC Output Continuous Current 29.5 A 24 A
AC Output Frequency 50.0 ±0.1 Hz
Total Harmonic Distortion < 5% at rated power
Automatic Transfer Relay Rating 60 A
Auxiliary Relay Output 0–12 VDC, maximum 250 mA DC
Peak Efficiency 95.8% 95.8%
DC Input Voltage (Nominal) 48 VDC 48 VDC
DC Input Voltage Range 40–64 VDC 40–64 VDC
Maximum input DC current 180 A 150 A
Continuous Charge Rate at Nominal Voltage 140 A 110 A
Power Factor Corrected Charging PF (0.98)