Conext XW+ 230V Installation Guide

Table Of Contents
Pre-Installation and Wall-Mounting
2–6 975-0714-01-01
This manual is for use by qualified personnel only
For more information, see “AUX Port” on page 3–4 of this Guide.
Wall-Mounting
A mounting plate is included with each Conext XW+ Inverter/Charger and Conext
XW+ Power Distribution Panel designed to meet standards for structural and
seismic stability.
Each Conext XW+ and PDP requires a separate mounting plate. Attach the
mounting plate to the wall before you attach the Conext XW+ to the mounting
plate.
Each mounting plate requires a minimum of four 6 mm diameter lag bolts or other
fasteners (not included).The fasteners must be strong enough to support 227 kg.
Figure 2-3 Air Filter and AUX Port Connector Installation
WARNING
HEAVY EQUIPMENT
The Conext XW+ Inverter/Charger can cause serious injury if it falls or is
dropped on a person.
For structural and seismic stability, the Conext XW+ Inverter/Charger must be
mounted onto a vertical supporting surface strong enough to support a
minimum of 227 kg.
Failure to follow these instructions can result in death or serious injury.
AUX port
Air vent
Air filter
AUX port connector