Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Pre-Installation and Wall-Mounting
2–12 975-0714-01-01
This manual is for use by qualified personnel only
Communications Network Preparation
To separate the communications cables and signal cables from the DC and AC
wiring, a raceway (wire barrier) has been included in the design of the Conext
Conext XW+ Conduit Box.
This raceway is built into the bottom of the Conext XW+ Conduit Box (see Figure
2-10, below) and is held in place by a single screw at the top of the raceway.
Before making AC and DC connections, route communication cables (including
Battery Temperature Sensor) through the raceways. For easier identification, use
a different color for each communications cable, or cable tags.
Connect communications cables to their components after AC and DC
connections are made.
WARNING
XANBUS SHOCK HAZARD
Xanbus cables in contact with DC or AC power can transmit an electric shock.
Do not route the Xanbus cables in the same conduit or panel as the AC and
DC power cabling.
Failure to follow these instructions can result in death or serious injury.
Figure 2-10 Example of raceways in a single-inverter system
Raceway Raceway
(Conduit Box) (PDP)