Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Pre-Installation and Wall-Mounting
2–16 975-0714-01-01
This manual is for use by qualified personnel only
Torque Va lues
Torque values for the Conext XW+ Inverter/Charger
Torque Values for the Conext XW+ Power Distribution Panel
Table 2-4 Torque Values for AC Wiring (AC Terminals and Ground Bar)
Wire Size Torque Value
AWG mm
2
In-lb N-m
14–10 2.5–6 35 4.0
810404.5
6–4 16–25 45 5.1
Table 2-5 Torque Values for the Chassis Ground Lug
Wire Size Torque Value
AWG mm
2
In-lbs N-m
6–4 16–25 45 5.1
3–2 25–35 50 5.6
Table 2-6 Torque Values for the Inverter Battery Terminals
Torq ue Va l ue
Ft-lbs N-m
15 20.4
Table 2-7 Torque Values for AC Disconnects and AC Breakers
Wire Size Torque Value
AWG mm
2
In-lb N-m
16–10 1.31–6 45 5.1
810455.1
6–4 16–25 45 5.1
Tab le 2-8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus,
and DC Positive Bus in the Conext XW+ Power Distribution Panel
Wire Size Torque Value
AWG mm
2
In-lbs N-m
14–10 2.5–6 35 4.0
810404.5
6–4 16–25 45 5.1
3–2/0 25–35 50 5.6