Conext XW+ 230V Installation Guide

Table Of Contents
Pre-Installation and Wall-Mounting
2–16 975-0714-01-01
This manual is for use by qualified personnel only
Torque Va lues
Torque values for the Conext XW+ Inverter/Charger
Torque Values for the Conext XW+ Power Distribution Panel
Table 2-4 Torque Values for AC Wiring (AC Terminals and Ground Bar)
Wire Size Torque Value
AWG mm
2
In-lb N-m
14–10 2.5–6 35 4.0
810404.5
6–4 16–25 45 5.1
Table 2-5 Torque Values for the Chassis Ground Lug
Wire Size Torque Value
AWG mm
2
In-lbs N-m
6–4 16–25 45 5.1
3–2 25–35 50 5.6
Table 2-6 Torque Values for the Inverter Battery Terminals
Torq ue Va l ue
Ft-lbs N-m
15 20.4
Table 2-7 Torque Values for AC Disconnects and AC Breakers
Wire Size Torque Value
AWG mm
2
In-lb N-m
16–10 1.31–6 45 5.1
810455.1
6–4 16–25 45 5.1
Tab le 2-8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus,
and DC Positive Bus in the Conext XW+ Power Distribution Panel
Wire Size Torque Value
AWG mm
2
In-lbs N-m
14–10 2.5–6 35 4.0
810404.5
6–4 16–25 45 5.1
3–2/0 25–35 50 5.6