Torq ue Va lue s
975-0714-01-01 2–17
This manual is for use by qualified personnel only
Table 2 - 9 Torque Values for the power distribution jumpers in the Conext XW+
Power Distribution Panel
Wire Size Torque Value
AWG mm
2
In-lbs N-m
14–10 2.5–6 35 4.0
810404.5
6–4 16–25 45 5.1
3–2/0 25–35 50 5.6
Table 2-10 Torque Values for the Battery Cables to the DC Negative Bus, and DC
Positive Bus in the Conext XW+ Power Distribution Panel
Torque Value
Ft-lbs N-m
15 20.4