Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Communication Ports and BTS Port
975-0714-01-01 3–5
This manual is for use by qualified personnel only
The 12 VDC output can be used to trigger a relay to disconnect batteries from
the inverter/charger when battery voltage or temperature are out of range.
The auxiliary output is also designed to provide the following functions:
• Auxiliary 12 VDC power supply. See AUX+12V Voltage Supply, below.
• Remote Power Off. See AUX-RPO: User Remote Power OFF (RPO), below.
AUX+12V Voltage Supply
DC voltage is available between JU-1 (AUX +12 V) and JU-3 (AUX-COM, signal
return). The power available at these terminals is 12 VDC and maximum current
is 250 mA (3 watts).
AUX+12 V and AUX-COM terminals can be used to power a relay
(3 watts maximum).
AUX +12 V voltage supply can be programmed for different tasks ON and OFF
using the Conext System Control Panel.
Default status of AUX+12 V is OFF.
AUX-RPO: User Remote Power OFF (RPO)
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through
an external switch (normal open contact) will provide the system shut off function
if the switch is closed. The external switch, if pressed, overrides the control
provided from the front panel.
To enable the AUX port remote power off function, enable the RPO setting from
the System Control Panel. For more information, see the
Conext XW+ Inverter/
Charger Owner’s Guide. If the external switch is cleared (not pressed), the
system can be enabled back from the front panel.
Select an external switch with normal open contact; consult your local system
designer or qualified technician for specific installation instructions.
Figure 3-3 AUX Port Location
AUX port
Note: Additional fuses may be necessary for some installations.