Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Wiring the Conext XW+ Inverter/Charger
3–6 975-0714-01-01
This manual is for use by qualified personnel only
User Line Wiring
Use twisted pairs of 0.2mm
2
to 3.31mm
2
(#24 AWG to #12 AWG) for connections.
Carefully route the wires away from high power load cables to minimize noise
effects on signal integrity.
AUX Port Terminal Assignments
Wiring the Conext XW+ Inverter/Charger without a PDP
This section provides instructions for making AC and DC connections without a
Conext XW+ Power Distribution Panel (PDP). For installations with a PDP, see
“Wiring the Conext XW+ Inverter/Charger with a PDP” on page 3–37.
Table 3-1 User Connector Terminals and Functions
Pin Reference Name Function
JU-1 AUX+12V +12 V User
Voltage Supply
+12 VDC Voltage source: 250 mA
maximum
JU-2 AUX-RPO Remote Power
Off
Remote Power Off Logic Level:
Active Low. Activating this signal
shuts down system operation.
JU-3 AUX-COM Common
Ground
Reference
Return Common Ground
Reference for 12 V, Remote Power
Off signals.
JU-4 EXT_TS_OUT External
Transfer switch:
Output signal
Open collector type drive circuit
(30V/0.5A max)
JU-5 EXT_TS_IN External
Transfer switch:
Input signal
External Transfer switch: Low
signal range:(0-5V) High signal
range:10-28V with the
consumption of 8mA@12V and
10mA@24V.
NOTICE
OVERLOADING THE DISTRIBUTION PANEL
The amount of power that can be fed into a distribution panel and the means
and location for feed-in, must be in accordance with the current requirements
of your local electrical code.
Failure to follow these instructions can result in damage to equipment.
Note: If a Conext XW+ Conduit Box is installed, run the communication and
Battery Temperature Sensor cables through the raceway at the rear of the Conext
XW+ Conduit Box making AC and DC connections. The raceways become more
difficult to access after AC and DC wiring is completed.
For more information,
see “Communications Network Preparation” on page 2–12 of this Guide.