Conext XW+ 230V Installation Guide

Table Of Contents
Wiring the Conext XW+ Inverter/Charger
3–12 975-0714-01-01
This manual is for use by qualified personnel only
Battery cables are not included in the Conext XW+ Inverter/Charger package.
Depending on your installation requirements, you will need to supply at least one
pair of battery cables. For battery cable requirements, see “Battery Cable
Requirements” on page 2–14.
NOTICE
DC REVERSE POLARITY
Before making the final DC connection or closing the DC breaker or
disconnect, check cable polarity at both the battery and the inverter/charger.
Positive (+) must be connected to positive (+). Negative (–) must be
connected to negative (–).
Failure to follow these instructions can result in damage to equipment.
Figure 3-6 Battery terminals (bottom of Conext XW+)
Figure 3-7 Battery cable connection
Positive (+)
Battery terminal
(Red)
Negative (–)
Battery terminal
(Black)
Terminal surface
Battery cable lug
Flat washer
Split-ring washer
3/8-16 x 5/8” bolt
(included)
Copper compression lug