Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Wiring the Conext XW+ Inverter/Charger
3–24 975-0714-01-01
This manual is for use by qualified personnel only
To connect the Conext XW+ Inverter/Charger to the main utility panel:
1. See Figure 3-13 on page 3–24. Connect the neutral wire from the main utility
panel to the inverter GRID (AC1) neutral terminal.
2. Connect the AC LINE wire from the main utility panel to the inverter GRID
(AC1) L terminal.
To connect the Conext XW+ Inverter/Charger to the AC generator:
1. See Figure 3-14. Connect the ground wire from the generator breaker or
disconnect to the inverter’s ground bus terminal.
2. Connect the Neutral wire from the generator breaker or disconnect to the
inverter’s AC IN GEN (AC2) N terminal.
Figure 3-13 Wiring to the Inverter Load Sub-Panel or Utility Grid (no PDP)
1. Primary ground system
2. Inverter load sub-panel
3. Main utility panel
Actual wiring requirements may vary.
Cable routing may vary. See Knockout Selection
on page 2-4 and Communications Network
Preparation on page 2-12.
For torque values, see page 2-16 and 2-17.
Grounding
wire
Neutral
Line (L)
AC INAC OU T AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
LIVE IN
LIVE OUT
N
G
1
2
3
N
G
LEGEND