Wiring the Conext XW+ Inverter/Charger
3–24 975-0714-01-01
This manual is for use by qualified personnel only
To connect the Conext XW+ Inverter/Charger to the main utility panel:
1. See Figure 3-13 on page 3–24. Connect the neutral wire from the main utility
panel to the inverter GRID (AC1) neutral terminal.
2. Connect the AC LINE wire from the main utility panel to the inverter GRID
(AC1) L terminal.
To connect the Conext XW+ Inverter/Charger to the AC generator:
1. See Figure 3-14. Connect the ground wire from the generator breaker or
disconnect to the inverter’s ground bus terminal.
2. Connect the Neutral wire from the generator breaker or disconnect to the
inverter’s AC IN GEN (AC2) N terminal.
Figure 3-13 Wiring to the Inverter Load Sub-Panel or Utility Grid (no PDP)
1. Primary ground system
2. Inverter load sub-panel
3. Main utility panel
Actual wiring requirements may vary.
Cable routing may vary. See Knockout Selection
on page 2-4 and Communications Network
Preparation on page 2-12.
For torque values, see page 2-16 and 2-17.
Grounding
wire
Neutral
Line (L)
AC INAC OU T AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
LIVE IN
LIVE OUT
N
G
1
2
3
N
G
LEGEND