Conext XW+ 230V Installation Guide

Table Of Contents
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0714-01-01 3–37
This manual is for use by qualified personnel only
Wiring the Conext XW+ Inverter/Charger with a PDP
This section provides instructions for making AC and DC connections between
the Conext XW+ Inverter/Charger and a Conext XW+ Power Distribution Panel,
using the cables that are included with the PDP
and Conext XW+ Connection Kit.
Note: AC breakers are not included with the Conext XW+ Inverter/Charger or
Conext XW+ Power Distribution Panel. You will need to provide your own
appropriately sized and rated AC breakers. For more information, contact your
local Schneider Electric Sales Representative.
Note: The dual and triple inverter installation steps described in this section
require a Conext XW+ Connection Kit (part number 865-1020-02) for each
additional Conext XW+ Inverter/Charger.
For more information, contact your local Schneider Electric Sales Representative
or visit our website at: http://solar.schneider-electric.com/tech-support/
Note: The Conext XW+ Power Distribution Panel may not be available in all
regions; installation is dependent upon your local electrical code. Consult your
local electrical authority to ensure your installation is code-compliant.
NOTICE
EQUIPMENT DAMAGE
Be sure to finish all wiring (AC, DC, Xanbus, communications) when installing
additional Conext XW+ units including “Installing AC sync and Xanbus cables”
on page 4–5 prior to powering up the system.
Failure to follow these instructions can result in equipment damage.