Conext XW+ 230V Installation Guide

Table Of Contents
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0714-01-01 3–41
This manual is for use by qualified personnel only
Conext XW+ Inverter/Charger Grounding
The Conext XW+ is provided with ground terminals that must be reliably
connected to ground (protective earth) by appropriately sized equipment
grounding conductors. System grounding for the AC and DC systems must be
done according to all applicable local installation codes.
For more information about system grounding, see “Grounding the DC System”
on page 3–7 and “AC Equipment Grounding” on page 3–20.
Making DC Connections with a PDP
Battery Cables and Battery Terminals
WARNING
UNGROUNDED EQUIPMENT
Equipment ground terminals must be reliably connected to ground by
appropriately sized grounding conductors. All installations must comply with
national and local codes. Consult local and national codes for specific
grounding and bonding requirements.
Failure to follow these instructions can result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See EN 50110.
This equipment must only be installed and serviced by qualified electrical
personnel.
Never operate energized with covers removed
Energized from multiple sources. Before removing covers identify all
sources, de-energize, lock-out, and tag-out and wait 2 minutes for circuits
to discharge
Always use a properly rated voltage sensing device to confirm all circuits
are de-energized.
Failure to follow these instructions will result in death or serious injury.