Conext XW+ 230V Installation Guide
Table Of Contents
- Conext™ XW
- Inverter/Charger
- Conext™ XW
- Inverter/Charger
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Conext XW+ Features
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Battery Fuse Disconnect Box (250A)
- Battery Fuse Disconnect Box (160A)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Basic Functional Test – Single Inverter
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Pre-Installation Steps
- Conext XW+ Power Distribution Panel Internal Faceplate Removal
- Conext XW+ Inverter/Charger Grounding
- Making DC Connections with a PDP
- Single Inverter/Charger DC Connections
- Dual Inverter/Charger DC Connections
- Triple Inverter/Charger DC Connections
- AC Wiring with a Conext XW+ Power Distribution Panel
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
Wiring the Conext XW+ Inverter/Charger
3–42 975-0714-01-01
This manual is for use by qualified personnel only
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Remove watches, rings, or other metal objects.
• This equipment must only be installed and serviced by qualified electrical
personnel.
• Keep sparks and flames away from the batteries.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or other metal parts on top of batteries.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery Circuit Breakers must be installed according to the specifications
and requirements defined by Schneider Electric.
• Servicing of batteries must only be performed by qualified personnel
knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect the charging source prior to connecting or disconnecting
battery terminals.
Failure to follow these instructions will result in death or serious injury.
WARNING
OVERHEATING OF DC TERMINALS AND CABLES
• Overheating of the DC terminals or DC cables to dangerous temperatures
may occur due to improper installation.
• Do not put anything between the cable lug and the terminal surface.
• Do not over-tighten connections; observe all recommended torque values.
• Do not apply any type of anti-oxidant paste until after the cable connection
is tightened.
• Do not under size cables; install cables sized in accordance with national
electrical code requirements.
• DC cables must have crimped copper compression lugs or crimped and
soldered copper compression lugs; soldered connections alone are not
acceptable. Lugs must be rated for use with fine-stranded cable.
• Do not use coarse-stranded cable; the lack of flexibility may pull DC
terminal connections loose.
Failure to follow these instructions can result in death or serious injury.