Conext XW+ 230V Installation Guide

Table Of Contents
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0714-01-01 3–43
This manual is for use by qualified personnel only
See “Battery Cables and Battery Terminals” on page 3–10.
DC Grounding
See “Grounding the DC System” on page 3–7.
Single Inverter/Charger DC Connections
To connect the Conext XW+ Power Distribution Panel (PDP) to the Conext
XW+ Inverter/Charger:
1. Connect the positive battery cable (pre-installed in the PDP) to the positive
battery terminal at the bottom of the Conext XW+, as shown in Figure 3-23 on
page 3–45.
2. Connect the negative battery cable (pre-installed in the PDP) to the negative
battery terminal at the bottom of the Conext XW+ Inverter/Charger.
3. Attach the DC terminal covers (included with the Conext XW+ Inverter/
Charger) to the bottom of the Conext XW+ DC terminals.
NOTICE
DC REVERSE POLARITY
Before making the final DC connection or closing the DC breaker or
disconnect, check cable polarity at both the battery and the inverter/charger.
Positive (+) must be connected to positive (+). Negative (–) must be
connected to negative (–).
Failure to follow these instructions can result in damage to equipment.
WARNING
UNGROUNDED EQUIPMENT
Equipment ground terminals must be reliably connected to ground by
appropriately sized grounding conductors. All installations must comply with
national and local codes. Consult local and national codes for specific
grounding and bonding requirements.
Failure to follow these instructions can result in death or serious injury.
Note: When making the connections, be sure to observe correct hardware
stacking and proper polarity, and ensure that nothing obstructs the connection
between the terminal surface and the battery cable lug. (See Figure 3-7 on page
3–12.)