Wiring the Conext XW+ Inverter/Charger
3–48 975-0714-01-01
This manual is for use by qualified personnel only
Triple Inverter/Charger DC Connections
DC Grounding
See “Grounding the DC System” on page 3–7.
DC Positive Bus Bar installation
1. Remove the existing bus bar from the bottom terminal of the GJ250A 160
VDC, 3/8" stud DC disconnect/breaker (pre-installed in the PDP).
2. Install a second and third GJ250A - DC rated breaker (included with the
Conext XW+ Connection Kits) next to the
existing DC disconnect/breaker.
3. Install the DC positive bus bar included with the Conext XW+ Connection Kit.
(This DC positive bus bar supports up to three GJ250A - DC rated breakers.)
4. Remove the appropriate knockouts from the Conext XW+ Power Distribution
Panel lower faceplate.
DC Wiring for a Triple-Inverter System
1. Using the instructions provided in “Single Inverter/Charger DC Connections”
on page 3–43, make DC connections from the Conext XW+ Power
Distribution Panel to:
a) the first Conext XW+ Inverter/Charger (INV1) and
b) the battery bank.
2. Connect the positive battery cable for INV2 (included with the Conext XW+
Connection Kit) to the top terminal on the second DC disconnect/breaker.
3. Connect the negative battery cable for INV2 (included with the Conext XW+
Connection Kit) to the DC Negative Bus.
4. Connect the positive battery cable to the positive terminal on the second
Conext XW+ (INV2) and the negative battery cable to the negative terminal
on INV2.
WARNING
UNGROUNDED EQUIPMENT
Equipment ground terminals must be reliably connected to ground by
appropriately sized grounding conductors. All installations must comply with
national and local codes. Consult local and national codes for specific
grounding and bonding requirements.
Failure to follow these instructions can result in death or serious injury.
Note: Replace faceplates after AC and DC wiring is complete.
Note: One pair of battery cables is included with each Conext XW+ Connection
Kit and Conext XW+ Power Distribution Panel.
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in “AC Wiring with a Conext XW+ Power Distribution Panel” on
page 3–50.