Conext XW+ 230V Installation Guide

Table Of Contents
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0714-01-01 3–49
This manual is for use by qualified personnel only
5. Connect the positive battery cable for INV3 (included with the Conext XW+
Connection Kit) to the top terminal on the third DC disconnect/breaker.
6. Connect the negative battery cable for INV3 (included with the Conext XW+
Connection Kit) to the DC Negative Bus.
7. Connect the positive battery cable to the positive terminal on INV3 and the
negative battery cable to the negative terminal on INV3.
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in “AC Wiring with a Conext XW+ Power Distribution Panel” on
page 3–50.
Figure 3-25 DC Connections for a Triple-Inverter System with PDP
AC INAC O UT AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
AC INAC O UT AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
AC INAC O UT AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
AC INAC OUT AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NLNLNL
1
1. Battery Actual wiring requirements may vary.
Cable routing may vary. See Knockout Selection
on page 2-4 and Communications Network
Preparation on page 2-12.
For torque values, see page 2-16 and 2-17.
LEGEND
Grounding
conductor
Positive (+)
Battery cable
Negative ()
Battery cable
BTS cable
INV1INV2INV3