Specifications
The STB NIP 2212 NIM
32
890USE17700 September 2003
off blink: 2 off Assignment error—the NIM has detected a module
assignment error; the island bus is not started.
blink: 5 Internal triggering protocol error.
off blinking
(steady)
off Fatal error—Because of the severity of the error, no further
communications with the island bus are possible and the NIM
stops the island. The following are fatal errors:
significant internal error
module ID error
auto-addressing (See Auto-Addressing, p. 46) failure
mandatory module (See Configuring Mandatory Modules,
p. 154) configuration error
process image error
auto-configuration/configuration (See Auto-Configuration,
p. 49) error
island bus management error
receive/transmit queue software overrun error
on off off The island bus is operational.
on blink: 3 off At least one standard module does not match—the island bus
is operational with a configuration mismatch.
on blink: 2 off Serious configuration mismatch (when a module is pulled
from a running island)—the island bus is now in pre-
operational mode because of one or more mismatched
mandatory modules.
blink: 4 off off The island bus is stopped (when a module is pulled from a
running island)—no further communications with the island
are possible.
off on off Fatal error—internal failure.
[any] [any] on Test mode is enabled—the configuration software or an HMI
panel can set outputs. (See 2.)
1 The TEST LED is on temporarily during the Flash overwrite process.
2 The TEST LED is on steadily while the device connected to the CFG port is in control.
RUN
(green)
ERROR
(red)
TEST
(yellow)
Meaning