Instruction manual
Timers
114
890USE18300 September 2003
Time Units and
Terminal Count
You need to preset the timer block to accumulate in one of the following time units:
1ms
10 ms
100 ms
1000 ms
10 000 ms
When the timer block is enabled and the trigger starts the accumulation, the block
will count a specified number of time units. The maximum number of unit counts
allowed is called the terminal count. The terminal count is a user-specified integer
value in the range 1 to 32 767.
When the block reaches the terminal count, the accumulator stops counting time
units and the output of the action turns off (0 if the output is standard, 1 if the output
is inverted). The output remains off as long as the timer accumulator holds the
terminal count.
For example, suppose you specify a time unit of 10 ms and a terminal count of 24.
When the timer trigger input drops from 1 to 0, the timer accumulates to 240 ms,
then stops and holds its terminal count as long as the trigger remains at 0.
As the timing diagram above shows, the standard output falls to 0 (the inverted
output rises to 1) when the terminal count is reached. The standard output remains
0 (the inverted output remains 1) while the timer holds the terminal count. The
standard output is 1 (the inverted output is 0) whenever the timer is not at the
terminal count.
timer trigger
timer
0
0
1
0
1
output
24
240 ms
0
1
output
inverted