Instruction manual

Digital Latches
158
890USE18300 September 2003
Operational
Input
The operational input is a stream of Boolean 1s and 0s that can be latched and
unlatched by the latch trigger. It may be produced by:
a constant
a digital input from a module on the island
a digital output from the virtual module
an output on the action module written to by the fieldbus master
if the latch is the second block in a nested reflex action (See Nesting Two Reflex
Blocks, p. 36), the latch trigger input may be the output from the first reflex block
The following timing diagram shows how the value of the trigger effects the output
from the block:
At the beginning of the timing sequence, the standard output echoes the value of the
operational input (the inverted output echoes the inverse of the operational input) as
long as the trigger is high. When the trigger drops from 1 to 0 the first time, the
operational input is low. The trigger latches the standard output at 0 (the inverted
output at 1), and holds it there as long as the trigger stays low.
When the latch trigger rises back to 1, the standard output begins to echo the
operational input again (the inverted output echoes the inverse of the operational
input again).
When the latch trigger falls from 1 to 0 the second time, the operational input is high.
The trigger latches the standard output at 1 (the inverted output at 0).
operational input
latch_trigger
0
0
1
0
1
output
1
0
1
output
inverted