Instruction manual
Introduction
890USE18300 September 2003 37
The Logical
Outputs
The output from each block also needs to be assigned a logical output. The logical
output is a tag name for the output—a text string between one and eight characters
long. The characters may be any combination of standard keyboard characters—
alpha numerics, underscores, and/or standard symbols (!,?, /, >, etc.).
The logical output can be particularly useful in a nested reflex because the text string
of the first action block will appear in the pull-down menu as an input to the second
action block.
A Counter-
Compare
Configuration
To clarify the process of configuring a nested action, let’s look at the way you might
configure the first of the two action blocks in the reflex editor of the Advantys
configuration software:
Action no. 1 is a falling-edge counter, as items 1 and 2 above indicate. The action
module is the STB DDO 3230 digital output module at island bus address 2 (item 3
above). The action module needs to be a digital output module because the ultimate
result of the nested action will be Boolean.
Item 4 above shows the physical output channel on the action module as None. The
output from the falling-edge counter is sent to a temporary memory buffer. The
output value is then used as an operational input to the second block in the nested
action.
1
1
1
2
1
3
1
4
1
5
R1