Datasheet

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Mar 08, 2018
1
Product datasheet
Characteristics
A9F06313
iC60H - miniature circuit breaker - 3P - 13A - B
curve
Main
Device application Distribution
Range Acti 9
Range of product IC60
Product name Acti 9 iC60
Product or component type Miniature circuit-breaker
Device short name IC60H
Poles description 3P
Number of protected poles 3
[In] rated current 13 A
Network type AC
DC
Trip unit technology Thermal-magnetic
Curve code B
Breaking capacity code H
Breaking capacity 10 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
15 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
30 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
10000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
42 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz
42 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
15 kA Icu conforming to EN/IEC 60947-2 - <= 180 V DC
Utilisation category Category A conforming to EN 60898-1
Category A conforming to IEC 60898-1
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Yes conforming to EN 60898-1
Yes conforming to IEC 60898-1
Standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2

Summary of content (3 pages)