Faults - Causes - Remedies
Assistance with maintenance, fault display
If a problem arises during setup or operation, ensure that the recommendations relating to the environment,
mounting and connections have been observed.
The first fault detected is stored and displayed, flashing, on the screen: the drive locks and the fault relay (R1A -
R1C or R2A - R) contact opens.
Drive does not start, no fault displayed
• If there is no display, check the power supply to the drive, the wiring of inputs AI1 and AI2 and the RJ45
connection.
• Other cases: Please refer to the CD-ROM.
9IH Motor torque
100% = nominal motor torque
HI4 Operating time 0 to 65530 hours
Total time the motor has been powered up:
0 to 9999 (hours), then 10.00 to 65.53 (kilo-hours).
Can be reset to zero by the rPr parameter in the FLt- menu (please refer to the CD-ROM).
/9@ Terminal locking code
Please refer to the CD-ROM.
I<; Auto-tuning status
I->: The default stator resistance value is used to control the motor.
:1D@: Auto-tuning has been requested but not yet performed.
:H93: Auto-tuning in progress
2-57: Auto-tuning has failed.
@9D1: The stator resistance measured by the auto-tuning function is used to manage driving.
<@: Indicates the ATV31 software version
E.g.: 1102 = V1.1 IE02.
75-! Logic input functions
Please refer to the CD-ROM.
-5-! Analog input functions
Please refer to the CD-ROM.
Code Description Variation range