Faults to be reset
The cause of the fault should be rectified before resetting by powering down until the display goes out, then
switching on again.
Fault Probable cause Remedy
/92
CANopen fault
CANopen bus communication
interrupted
Check the communication bus.
Please refer to the product-specific
documentation.
/H2
capacitor load circuit
Load relay control fault or charging
resistor damaged
Replace the drive.
112
EEPROM fault
internal memory fault Check the environment
(electromagnetic compatibility).
Replace the drive.
5D2
internal fault
Short-circuit on 10 V supply
Internal fault
Check the circuits connected to the 10 V.
Check the wiring of inputs AI1 and AI2
and the RJ45 connection.
Check the environment
(electromagnetic compatibility).
Replace the drive.
722
Loss of 4-20mA
Loss of the 4-20 mA reference on input
AI3
Check the connection on input AI3.
9>2
overvoltage
during deceleration
Braking too sudden
Driving load
Increase the deceleration time.
Install a braking resistor if necessary.
See the brA function (please refer to the
CD-ROM).
9/2
overcurrent
Incorrect parameters in the SEt- and
drC- menus
Inertia or load too high
Mechanical locking
Check the SEt- and drC- parameters.
Check the size of the motor/drive/load.
Check the state of the mechanism.
942
drive overload
Drive temperature too high Check the motor load, the drive
ventilation and the environment. Wait
for the drive to cool down before
restarting.
972
motor overload
Triggered by excessive motor current
Incorrect value for parameter rSC
Check the ItH setting (motor thermal
protection) (page 31), check the motor
load. Wait for the drive to cool down
before restarting.
Re-measure rSC (see page 33).
9:2
motor phase break
Loss of phase at drive output
Downstream contactor open
Motor not connected or motor power
too low
Instantaneous instability in the motor
current
Check the connections from the drive to
the motor.
If a downstream contactor is being
used, set OPL to OAC (please refer to
the CD-ROM, FLt- menu).
Test on a low power motor or without a
motor: set OPL to nO (please refer to
the CD-ROM, FLt- menu).
Check and optimise the UFr (page 31),
UnS and nCr (page 33) parameters and
perform auto-tuning with tUn (page 34).
9;2
overvoltage
Line voltage too high
Disturbed line supply
Check the line voltage.