User Manual
1624580 09/2009 39
ENGLISH
Faults to be reset
The cause of the fault should be rectified before resetting by powering down until the display goes out, then
switching on again.
Fault Probable cause Remedy
/92
CANopen fault
• CANopen bus communication
interrupted
• Check the communication bus.
• Please refer to the product-specific
documentation.
/H2
capacitor load circuit
• Load relay control fault or charging
resistor damaged
• Replace the drive.
112
EEPROM fault
• internal memory fault • Check the environment
(electromagnetic compatibility).
• Replace the drive.
5D2
internal fault
• Short-circuit on 10 V supply
• Internal fault
• Check the circuits connected to the 10 V.
• Check the wiring of inputs AI1 and AI2
and the RJ45 connection.
• Check the environment
(electromagnetic compatibility).
• Replace the drive.
722
Loss of 4-20mA
• Loss of the 4-20 mA reference on input
AI3
• Check the connection on input AI3.
9>2
overvoltage
during deceleration
• Braking too sudden
• Driving load
• Increase the deceleration time.
• Install a braking resistor if necessary.
• See the brA function (please refer to the
CD-ROM).
9/2
overcurrent
• Incorrect parameters in the SEt- and
drC- menus
• Inertia or load too high
• Mechanical locking
• Check the SEt- and drC- parameters.
• Check the size of the motor/drive/load.
• Check the state of the mechanism.
942
drive overload
• Drive temperature too high • Check the motor load, the drive
ventilation and the environment. Wait
for the drive to cool down before
restarting.
972
motor overload
• Triggered by excessive motor current
• Incorrect value for parameter rSC
• Check the ItH setting (motor thermal
protection) (page 31), check the motor
load. Wait for the drive to cool down
before restarting.
• Re-measure rSC (see page 33).
9:2
motor phase break
• Loss of phase at drive output
• Downstream contactor open
• Motor not connected or motor power
too low
• Instantaneous instability in the motor
current
• Check the connections from the drive to
the motor.
• If a downstream contactor is being
used, set OPL to OAC (please refer to
the CD-ROM, FLt- menu).
• Test on a low power motor or without a
motor: set OPL to nO (please refer to
the CD-ROM, FLt- menu).
• Check and optimise the UFr (page 31),
UnS and nCr (page 33) parameters and
perform auto-tuning with tUn (page 34).
9;2
overvoltage
• Line voltage too high
• Disturbed line supply
• Check the line voltage.