User Manual

40 1624580 09/2009
ENGLISH
Faults which can be reset as soon as their cause disappears
:42
input phase failure
Failure of one phase
3-phase ATV31 used on a single phase
line supply
Unbalanced load
This protection only operates with the
drive on load.
Check the connection and the fuses.
Use a 3-phase line supply.
Disable the fault by setting IPL = nO
(please refer to the CD-ROM)
;/2
motor short-circuit
Short-circuit or earthing at the drive
output
Significant earth leakage current at the
drive output if several motors are
connected in parallel
Check the cables connecting the drive
to the motor, and the motor insulation.
Reduce the switching frequency.
Connect chokes in series with the
motor.
;72
Modbus fault
Modbus bus communication
interrupted
Confirmation of remote terminal
LCC = YES and terminal disconnected
Check the communication bus.
Please refer to the product-specific
documentation.
Check the display terminal connection.
;92
overspeed
Instability
Driving load too high
Check the motor, gain and stability
parameters.
Add a braking resistor.
Check the size of the motor/drive/load.
ID2
auto-tuning fault
Special motor or motor whose power is
not suitable for the drive
Motor not connected to the drive
Use the L or the P ratio (Uft page 34).
Check the presence of the motor during
auto-tuning.
If a downstream contactor is being
used, close it during auto-tuning.
Fault Probable cause Remedy
/22
configuration fault
The current configuration is
incompatible.
Return to factory settings or call up the
backup configuration, if it is valid. See
parameter FCS in the drC- menu, page
35.
/25
configuration fault via
serial link
Invalid configuration (the configuration
loaded in the drive via the serial link is
incompatible).
Check the configuration loaded
previously.
Load a compatible configuration.
<;2
undervoltage
Line supply too low
Transient voltage dip
Damaged load resistor
Check the voltage and the voltage
parameter.
Replace the drive.
Fault Probable cause Remedy