Specifications

© 2012 Schneider Electric (Australia)
PICED FAQ
Page 9
·
Use the Diagnostic Software Traffic Analyser to look at the amount of traffic and error rates
Solution #4
You may have several faulty units. Check the C-Gate log for units which have failed.
Note that the
View | Component Label | Show Network States
menu item can be used to show
the state of the network associated with each Component in your project.
1.2.1.7 C-Gate Messages
The C-Gate log file records details of what is happening on C-Bus. Refer to the Advanced Fault
Diagnosis document (c:\Clipsal\Frequently Asked Questions\Manuals\Advanced Fault Diagnosis.
pdf) for details of the messages.
1.2.2 Networks
1.2.2.1 C-Bus Networks
Problem
How do you find out more about C-Bus Networks ?
Solution
Refer to the C-Bus Networks document. It can be found on the Schneider Electric (Australia) web
site at http://www3.clipsal.com/cis/lit_installtraining_trainmanuals.php3
1.2.2.2 Using More than 255 Groups
Problem
More than 255 Group Addresses are needed.
Solution
The maximum number of Group Addresses available is 255 per Application per Network. If you
need to use more than 255 Group Addresses, there are two options :
·
Use another Application ($30 to $5F are available for lighting)
·
Use another Network
Using multiple Networks adds complications, but may be necessary anyway if there are too many
units for a single Network. Even if multiple Networks are used, it may be desirable to use a
different Application on each Network so that there are not unforeseen interactions between the
Networks.
For example, if you use Group Address 20 on Application $38 (56 decimal) on two different
Networks which are connected by a C-Bus bridge, then these two Group Addresses may or may
not be independent, depending on the bridge configuration. C-Touch will assume that the
Networks are fully connected with C-Bus bridges. This means that it will assume Group Address
20 on one Network is the same as Group Address 20 on another Network, although in reality they
may be different. If you use Group Address 20 on different Applications, then C-Touch will always
treat them as being independent (which they will be).
Refer to the
C-Bus Networks
document available from the Schneider Electric (Australia) web site
for more information.