Specifications

© 2012 Schneider Electric (Australia)
PICED FAQ
Page 15
1.3.1.7 C-Touch Resetting
Problem
C-Touch is resetting itself.
Solution 1
If the a C-Touch unit continuously resets itself, the initialisation of the C-Bus interface has probably
failed. The most likely causes are :
·
No clock on the C-Bus network
·
Poor communication on C-Bus (check the burden)
·
Low C-Bus Voltage (less than 20V) and/or low temperature (less than 5ºC)
If the unit has version 0.8 or earlier hardware, a short interruption of the C-Bus voltage (< 1
second) may also cause this symptom. In this case, remove C-Bus voltage for more than 2
seconds, then re-apply.
Solution 2
This may also be caused by a low C-Bus voltage at the C-Touch. In this case, it may be necessary
to change the network wiring or power supplies.
1.3.1.8 C-Touch Ticking
Problem
C-Touch (Mark 1) is ticking and displaying nothing on the screen.
Cause
The firmware has been corrupted (probably due to an interruption during download of new
firmware).
Solution
Download the latest firmware and reload the project.
1.3.1.9 Please Program Before Use Message
Problem
There is a message on C-Touch saying "Please Program Unit Before Use".
Cause
The user configuration data has been corrupted, probably caused by an interruption during
downloading a project.
Solution
Download a C-Touch project to C-Touch.
See also C-Touch Downloading Problems
1.3.1.10 C-Touch Connection Problems