PICED FAQ
Page 27
1.3.3.3 Using a PAC as a PCI
Problem
How can a PAC be used as a PC Interface ?
Solution
The USB driver for the PAC maps the USB connection to a serial port. When you plug a PAC into
the USB port of your computer, a serial port will be assigned. You can then use this serial port with
any software which is expecting a connection to a PCI, and the PAC will operate as a PCI.
Notes :
·
The PAC can not be used for its normal functions while operating as a PCI
·
To stop the PAC from operating as a PCI, you need to disconnect the USB cable.
See also
·
C-Touch as a PCI for details on setting hand-shaking lines
·
PAC Virtual Serial Port.
1.3.3.4 PAC Status LED
Problem
What does the flashing of the Status LED mean ?
Solution
Status LED Behaviour Meaning
Flashing 2.5 times per
second
Normal operation. LED changes state each time logic is run.
Flashing fast Fault with the firmware. Need to transfer new firmware and user
file.
Always on Fault with user configuration data file. Need to transfer new user
file.
Goes off for several seconds Logic has had a run-time error and the logic engine has had to
re-start. Most common cause is that the logic has taken too long
to execute.
Always off Logic is having an error on every scan. Most common cause is
that the logic has taken too long to execute.
1.3.3.5 Why doesn't my logic work ?
Problem
Why doesn't my logic work ?
Solution
There are many possible reasons for logic code not working as expected. Is is recommended that
you run the logic code with the PICED software first and fully test and debug it there. The PICED
software has more options available for resolving logic problems. When the logic is operating
correctly, then transfer it to the PAC.
The only features available in the PAC to support debugging are :