Schneider Electric C35 User Manual

Adjusting the C-Series Voltage Settings
975-0004-01-02 Rev D 25
The scale for the Low Voltage Disconnect setting is
calibrated as follows:
12-volt system: 10.5 to 12.5 volts
in increments of 0.2 volts,
24-volt system: 21.0 to 25.0 volts
in increments of 0.4 volts, and
48-volt system: 42.0 to 50.0 volts
in increments of 0.8 volts.