Characteristics
CA4KN40BW3
TeSys K control relay -
4 NO
- <= 690 V -
24 V DC
low consumption coil
Main
Range
TeSys
Product name
TeSys CAK
Product or component type
Control relay
Device short name
CA4K
Contactor application
Control circuit
Utilisation category
AC
-15
DC-13
Pole contact composition
4 NO
[Ue] rated operational voltage
<= 690 V <= 400 Hz
Control circuit type
DC low consumption
[Uc] control circuit voltage
24 V DC
Complementary
Coil technology
Built-in bidirectional peak limiting diode suppressor
[Ith] conventional free air thermal current
10 A at <= 50 °C
Irms rated making capacity
110 A conforming to IEC 60947
Associated fuse rating
10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660
[Ui] rated insulation voltage
690 V conforming to BS 5424
690 V conforming to IEC 60947
750 V conforming to VDE 0110 group C
600 V conforming to CSA C22.2 No 14
Mounting support
Plate
Rail
Connections - terminals
Screw clamp terminals 1 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 2 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 2 cable(s) 0.75...4 mm² - cable stiffness: flexible - without
cable end
Screw clamp terminals 1 cable(s) 0.75...4 mm² - cable stiffness: flexible - with cable
end
Screw clamp terminals 1 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - with
cable end
Screw clamp terminals 2 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - without
cable end
Tightening torque
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 6 mm
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit voltage limits
0.7...1.3 Uc at 50 °C operational
0.1...0.75 Uc at 50 °C drop-out
Operating time
10...20 ms coil de-energisation and NO opening
30...40 ms coil energisation and NO closing
Mechanical durability
30 Mcycles
Operating rate
6000 cyc/h
Immunity to microbreaks
2 ms
Inrush power in W
1.8 W at 20 °C
Hold-in power consumption in W
1.8 W at 20 °C
Heat dissipation
1.8 W
Minimum switching voltage
17 V
Minimum switching current
5 mA
Non overlap distance
0.5 mm
Insulation resistance
> 10 MOhm
Height
58 mm
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.