Datasheet

Product datasheet
Characteristics
CAD50P7
TeSys D control relay -
5 NO
- <= 690 V - 230 V AC
standard coil
Main
Range
TeSys
Product name
TeSys CAD
Product or component type
Control relay
Device short name
CAD
Contactor application
Control circuit
Complementary
Utilisation category
AC
-14
AC
-15
DC-13
Pole contact composition
5 NO
[Ue] rated operational voltage
<= 690 V AC 25...400 Hz
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
10 A at <= 60 °C
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current
100 A 1 s
120 A 500 ms
140 A 100 ms
Associated fuse rating
10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage
690 V conforming to IEC 60947-5-1
600 V certifications UL
600 V certifications CSA
Mounting support
Plate
Rail
Connections - terminals
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable
end
Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable
end
Tightening torque
1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit voltage limits
0.3...0.6 Uc drop-out
0.8...1.1 Uc operational 50 Hz
0.85...1.1 Uc operational 60 Hz
Operating time
12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NO opening
Mechanical durability
30 Mcycles
Operating rate
180 cyc/mn
Inrush power in VA
70 VA at 20 °C 50 Hz
Hold-in power consumption in VA
8 VA at 20 °C 50 Hz
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 2

Summary of content (2 pages)