Product Overview
2
[Ui] rated insulation voltage Power circuit 690V IEC 60947-4-1
Power circuit: 600V CSA certified
Power circuit: 600V UL certified
Signalling circuit 690V IEC 60947-1
Signalling circuit 600V CSA
Signalling circuit 600V UL
Electrical durability 0.6Mcycles 20A AC-1 <= 440 V
1Mcycles 9A AC-3 <= 440 V
Power dissipation per pole 1.56W AC-1
0.2W AC-3
Mounting support Rail
Plate
Connections - terminals Power circuit: screw clamp terminals 1 1…4mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 2 1…4mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 1 1…4mm² - cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 2 1…2.5mm² - cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 1 1…4mm² - cable stiffness: solid without
cable end
Power circuit: screw clamp terminals 2 1…4mm² - cable stiffness: solid without
cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible without
cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) flexible without
cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible with
cable end
Control circuit screw clamp terminals 2 0.00…0.00in² (1…2.5mm²) flexible with
cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) solid without
cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) solid without
cable end
Tightening torque Power circuit 15.05lbf.in (1.7N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05lbf.in (1.7N.m) screw clamp terminals Philips No 2
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals Philips No 2
Operating time 12...22 ms closing
4...19 ms opening
Safety reliability level B10d = 1369863cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 10Mcycles
Maximum operating rate 3600cyc/h 140°F (60°C)
Coil technology Without built-in suppressor module
Control circuit voltage limits Drop-out 0.3...0.6 Uc 50/60 Hz 158°F (70°C))
Operational 0.8...1.1 Uc 50 Hz 140°F (60°C))
Operational 0.85...1.1 Uc 60 Hz 140°F (60°C))
Operational 1...1.1 Uc 50/60 Hz 158°F (70°C))
Inrush power in VA 70VA 60 Hz 0.75 68°F (20°C))
70VA 50 Hz 0.75 68°F (20°C))
Hold-in power consumption in VA 7.5VA 60 Hz 0.3 68°F (20°C))
7VA 50 Hz 0.3 68°F (20°C))
Auxiliary contacts type Type mechanically linked 1 NO conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5mA for signalling circuit
Minimum switching voltage 17V signalling circuit
Non-overlap time 1.5Ms on de-energisation between NC and NO contact
1.5ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
Mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)
Height 3.03in (77mm)
Width 1.77in (45mm)
Depth 3.39in (86mm)
Net weight 0.71lb(US) (0.32kg)