Product Overview

2
Mounting support Rail
Plate
Connections - terminals Power circuit screw clamp terminals 1 flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible without
cable end
Power circuit screw clamp terminals 2 flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) flexible without
cable end
Power circuit screw clamp terminals 1 flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible with
cable end
Power circuit screw clamp terminals 2 flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00in² (1…2.5mm²) flexible with
cable end
Power circuit screw clamp terminals 1 solid without cable end
Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) solid without
cable end
Power circuit screw clamp terminals 2 solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) solid without
cable end
Control circuit screw clamp terminals 1 flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible without
cable end
Control circuit screw clamp terminals 2 flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) flexible without
cable end
Control circuit screw clamp terminals 1 flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) flexible with
cable end
Control circuit screw clamp terminals 2 flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00in² (1…2.5mm²) flexible with
cable end
Control circuit screw clamp terminals 1 solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²) solid without
cable end
Control circuit screw clamp terminals 2 solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²) solid without
cable end
Tightening torque Power circuit: 1.7N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals Philips No 2
Operating time 65.45...88.55 ms closing
20...30 ms opening
Safety reliability level B10d = 1369863cycles contactor with nominal load conforming to EN/ISO
13849-1
B10d = 20000000cycles contactor with mechanical load conforming to EN/ISO
13849-1
Mechanical durability 10Mcycles
Maximum operating rate 3600cyc/h 140°F (60°C)
Coil technology Without built-in suppressor module
Control circuit voltage limits Drop-out 0.1...0.3 Uc
Drop-out 0.1...0.3 Uc 158°F (70°C))
Operational 0.8...1.25 Uc
Operational 0.8...1.25 Uc 140°F (60°C))
Operational 1...1.25 Uc
Operational 1...1.25 Uc 158°F (70°C))
Inrush power in W 2.4W 68°F (20°C))
Hold-in power consumption in W 2.4W 68°F (20°C)
Auxiliary contacts type Mechanically linked 1 NO IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5mA signalling circuit
Minimum switching voltage 17V signalling circuit
Non-overlap time 1.5Ms on de-energisation between NC and NO contact
1.5ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm signalling circuit
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)
Height 3.03in (77mm)
Width 1.77in (45mm)