Part of Easy series Easy TeSys Catalog
90 years of leadership in motor starter technology Easy TeSys provides you Essential control & protection for your applications: HVAC Compressor Pumps Heating/ Furnace Material Handling Packaging Version 1.0 1st Feb.
Easy choice for simple applications 4 Version 1.0 1st Feb.
Easy TeSys > Easy TeSys™ contactors 9A to 32A Characteristics A-2 Accessories, spare parts A-9 Dimensions, mounting A-10 Characteristics B-2 Dimensions, mounting B-4 Presentation C-1 References C-1 Characteristics C-3 Dimensions, mounting C-5 Control motor and other loads > asy TeSys™ thermal E overload relays up to 32A Protect your load (direct mounting under contactors) > Easy TeSys™ Manual motor starters up to 32A Standalone & group applications Version 1.0 1st Feb.
Presentation, characteristics Presentation Easy TeSys contactors An easy solution for OEM’s, panel builders, contractors and system integrators who have a need for motor control, resistive load switching, and isolation applications. For use on conveyors, packaging, pumps, compressors, HVAC, refrigeration, furnace applications, and more! Easy TeSys contactors are ideal for these types of applications with power ratings and an operational life of approximately 1 million electrical operations.
Characteristics Easy TeSys contactors Environment Characteristics Contactor Type Rated insulation voltage (Ui) Rated impulse withstand voltage (Uimp) DPE 09…25 Conforming to IEC 60947-4-1, overvoltage category III, degree of pollution: 3 V 690 Conforming to UL, CSA V 600 Conforming to IEC 60947 kV 6 Conforming to standards DPE 32…38 IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No.
Characteristics Easy TeSys contactors Control Circuit Connection Characteristics Connection by Cable (Screw Clamp Connections) Contactor Type Flexible cable without cable end 1 conductor DPE 09…18 DPE 25 DPE 32 DPE 38 mm2 1…4 1…4 1…4 1…4 2 conductors mm2 1…4 1…4 1…4 1…4 Flexible cable with cable end 1 conductor mm2 1…4 1…4 1…4 1…4 2 conductors mm2 1…2.5 1…2.5 1…2.5 1…2.
Characteristics Easy TeSys contactors Control Circuit Characteristics, a.c. Supply Contactor Type Rated voltage of control circuit (Uc) 50/60 Hz Control voltage limits Operation Coils 50/60 Hz V Inrush a 60 Hz Inrush 0.75 0.75 70 70 0.3 0.3 7 7 0.75 0.75 70 70 0.3 0.3 VA 7.5 7.
Characteristics Easy TeSys contactors Characteristics of Auxiliary Contacts Incorporated in the Contactor Rated operational voltage (Ue) Up to V 690 Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 Conforming to UL, CSA V 600 Conventional thermal current (Ith) For ambient temperature ≤ 140ºF A (60ºC) 10 Frequency of the operational current Hz 25…400 Minimum switching capacity λ = 10-8 U min V 17 I min mA 5 Short-circuit protection Conforming to IEC 60947-5-1 Rated mak
Characteristics Easy TeSys contactors Auxiliary contact blocks Environment Characteristics For Use in Normal Operating Environments Type of Contact Block DPEAN Conforming to standards IEC 60947-5-1, NF C 63-140, EN 60947-5-1, UL 60947-5-1 and CSA C22.2 No.60947-5-1 Product certifications UL, CSA Protective treatment Conforming to IEC 60068 Degree of protection Conforming to VDE 0106 Ambient air temperature around the device Storage °F -76...176 (-60...80ºC) Operation °F 23...140 (-5...
Selection according to required electrical durability Easy TeSys contactors For utilisation categories AC-1 and AC-3 Millions of operating cycles DPE 32, DPE 38 DPE 25 DPE 18 10 8 DPE 12 DPE 09 Use in Category AC-1 (Ue ≤ 440 V) 6 4 2 1,5 1 0,8 0,6 0,4 0,2 0,1 4 6 7 8 10 20 25 32 40 50 60 80 100 Current broken in A Control of resistive circuits (cos j ≥ 0.95). The current broken (Ic) in category AC-1 is equal to the current (Ie) normally drawn by the load.
Selection according to required electrical durability Easy TeSys contactors For utilisation category AC-4 Millions of operating cycles DPE 38 DPE 32 DPE 25 1 0,8 DPE 18 DPE 09, DPE 12 Use in Category AC-4 (Ue ≤ 440 V) 0,6 0,4 0,2 0,1 0,08 Control of 3-phase asynchronous squirrel cage motors with breaking whilst motor stalled. The current broken in AC-4 is equal to 6 x Ie. (Ie = rated operational current of the motor).
References Easy TeSys contactors Accessories For 3-pole Reversing Contactors for Motor Control (1) + Description Reference Kit comprising: ■ 1 mechanical interlock without electrical interlocking. ■ 1 set of power connections. LAD9R1 Weight Lb 0.099 (0.045kg) Instantaneous Auxiliary Contact Blocks for Connection by Screw Clamp Terminals Description Number of NO Contacts per Block NC Reference Weight Contact blocks (clip-on front mounting) 2 1 DPEAN11 0.066 (0.
Dimensions, mounting Easy TeSys contactors Dimensions DPE 09…25 DPE 32 and 38 in. mm Minimum electrical clearance b b Minimum electrical clearance 0.39 10 c1 1.77 45 c 0.39 10 c1 c DPE 09…25 b 1.77 45 DPE 32 and 38 3.03 (77mm) b without add-on block 3.35 (85mm) c without add-on block 3.31 (84mm) c without add-on block 3.54 (90mm) c1 with DPEAN (2 contacts) 4.61 (117mm) c1 with DPEAN (2 contacts) 4.84 (123mm) 2xM4 b 2.36/2.76 60/70 e1 in.
Mounting, schemes Easy TeSys contactors Mounting DPE 09…38 on Mounting Rail AM1 DP200, DR 200 or AM1 DE200 (Width 1.38 in./35 mm) = = b b = = in. mm c c b DPE 09…25 DPE 32 and 38 3.03 (77mm) 3.35 (85mm) c (AM1-DP200 or DR200) 3.46 (88mm) 3.70 (94mm) c (AM1-DE200) 3.78 (96mm) 4.02 (102mm) = 2xM4 2xØ4,5 = c 1.38 35 = 1.97 50 1.97 50 = 1.38 35 = c = 2.36/2.76 60/70 = 2xM4 = = 1.97 50 DPE 09…25 DPE 32 and 38 3.39 (86mm) 3.62 (92mm) = in.
Version 1.0 1st Feb.
Presentation, description Easy TeSys thermal overload relays Presentation Easy TeSys thermal overload relays are designed to protect a.c. circuits and motors against: ■ overloads ■ phase failure ■ Iong starting time ■ prolonged stalled rotor condition. The thermal relay permanently controls the current driven by the motor. When this current exceeds the setting, its auxiliary contacts will change state, causing the motor to stop.
Characteristics Easy TeSys thermal overload relays 3-pole thermal overload relays Direct connection to Easy TeSys contactors Differential Thermal Overload Relays for Use with Fuses or Circuit Breakers ■ Compensated relays with manual or automatic reset ■ with relay trip indicator ■ for a.c Relay Setting Range (A) Fuses to Be Used with Selected Relay aM (A) For Use with Contactor Reference Weight Lb gG (A) Class 10 (1) for Connection by Screw Clamp Terminals 0.10…0.16 0.25 2 DPE09…32 DPER01 0.
Easy TeSys thermal overload relays Characteristics Power Circuit Characteristics Relay Type Ref. DPER 01...21 Size Tripping class Conforming to IEC 60947-4-1 Rated insulation voltage Conforming to IEC 60947-4-1 DPER 22...32 1 10 V 690 Rated impulse withstand voltage (Uimp) kV 6 Frequency limits Of the operating current Hz 50...60 Setting range Depending on model A 0.1...18 mm² 1.5...6 AWG 16...10 2.5...10 AWG 14...8 Flexible cable with cable end 1 conductor 1...4 AWG 18...10 1.5.
Characteristics Easy TeSys thermal overload relays Tripping Curves Average Operating Time Related to Multiples of The Setting Current Time Class 10 x the setting current (Ir) 1 Balanced operation, 3-phase, without prior current flow (cold state) 2 2-phase operation, without prior current flow (cold state) 3 Balanced operation, 3-phase, after a long period at the set current (hot state) DPER01...32 Direct Mounting Under DPE Contactors with Screw Clamp Connections in. mm b c 2.76 70 1.77 45 DPER01..
Presentation, References Protection components Easy TeSys manual motor controllers Presentation 1 2 3 Easy TeSys includes 3-pole thermal-magnetic circuit breakers conforming to IEC 60947-2 and IEC 60947-4-1. These devices also conform to UL 60947-4-1 as manual motor controllers and are suitable for the motor disconnect. Easy TeSys manual motor controllers are designed to control and protect motors. Connection These circuit breakers are designed for connection by screw clamp terminals.
References Protection components Easy TeSys manual motor controllers North American Short Circuit and Motor Group Ratings Model Overload Range Maximum RMS Short-Circuit Current, kA GP2E01 0.1-0.16 240 V+ 480 V+ 600 V+ 35 35 18 GP2E02 0.16-0.25 35 35 18 GP2E03 0.25-0.40 35 35 18 GP2E04 0.40-0.63 35 35 18 GP2E05 0.63-1.0 35 35 18 GP2E06 1.0-1.6 35 35 18 GP2E07 1.6-2.5 35 35 18 GP2E08 2.5-4.0 35 35 18 GP2E10 4.0-6.
Protection components Characteristics Easy TeSys manual motor controllers Environment Circuit Breaker Type GP2E Conforming to standards IEC 60947-2, IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1 Product certifications Protective treatment cUL, UL Listed Conforming to IEC 60068-2-30 IEC60068-2-30 Test Db, Variant 2 Degree of protection Ambient air temperature In GV2 MC01 enclosure: IP 41 In GV2 MC02 enclosure: IP 55 °F Storage Operation Flame resistance -4...140 (-20...
References Protection components Easy TeSys manual motor controllers Tripping Curves Average Operating Times at 20 °C Related to Multiples of the Setting Current Time (s) 10 000 1000 100 1 2 3 10 1 0,1 0,01 0,001 1 1,5 10 100 x the setting current (Ir) 1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state Contact Blocks Instantaneous Auxiliary Contacts GPEFC11 Mounting Maximum Number Type of Contacts Unit Reference Weight Lb Tightening Torque Side 2 N/O + N
Protection components Dimensions, mounting Easy TeSys manual motor controllers Dimensions GP2E = 3.50 89 1.77 45 = X1 in. mm 1.73 44 0.47 12 1.75 44.5 X1 0.63 16 2.60 66 X1: electrical clearance = 1.73 (40mm) for Ue ≤ 690 V Mounting GP2E on 1.38 (35mm) y rail in. mm 1.75 44.5 1.97/2.36 50/60 1.75 44.5 4,2 3.15 80 c 1.38 35 c = 3.09 (78.5mm) on AM1 DP200 (35 x 7.5) c = 3.39 (86mm) on AM1 DE200 and AM1 ED200 (35 x 15) GV2AF3, Combination GP2E + DPE Contactor in. mm 1.
Protection components Dimensions, mounting Easy TeSys manual motor controllers, in enclosure Dimensions Surface Mounting Enclosure GV2 MC0p in. mm = 5.12 130 147 = 2xØ0.20in.,3x0.25in. (1) 2xØ5mm, 3x6.3mm 3.31 84 3.66 93 = = (1) 4 knock-outs for 0.63 (16 mm) plastic cable gland or 0.63 (16 mm) conduit Version 1.0 1st Feb.
Schneider Electric Industries SAS 35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 € www.se.com Mar-2021 Document Number SEA10BD2210101EN © 2021 Schneider Electric. All Rights Reserved. Schneider Electric, TeSys, and Life Is On Schneider Electric are trademarks and the property of Schneider Electric, its subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners.