Brochure

C-3
Version 1.0 1st Feb. 2021
Easy TeSys catalog
Characteristics
Protection components
Easy TeSys manual motor controllers
Breaking Capacity
Circuit Breaker Type
GP2E
01 to 06 07 08 10 14 16 20 21 22 to 32
Rating A 0.1 to 1.6 2,5 4 6.3 10 14 18 23 25 to 32
Breaking capacity 230/240 V Icu kA g g g g g g g 30 30
conforming to IEC 60947-2 Ics %
(1)
g g g g g g g 100 100
400/415 V Icu kA g g g g g 10 10 10 10
Ics %
(1)
g g g g g 50 50 40 40
440 V Icu kA g g g 30 10 6 6 5 5
Ics %
(1)
g g g 100 100 50 50 50 50
500 V Icu kA g g g 30 8 5 5 3 3
Ics %
(1)
g g g 100 100 75 75 75 75
690 V Icu kA g 2 2 2 2 2 2 2 2
Ics %
(1)
g 75 75 75 75 75 75 75 75
g > 100 kA
(1) As % of Icu
Environment
Circuit Breaker Type GP2E
Conforming to standards IEC 60947-2, IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Product certications cUL, UL Listed
Protective treatment Conforming to IEC 60068-2-30 IEC60068-2-30 Test Db, Variant 2
Degree of protection In GV2 MC01 enclosure: IP 41
In GV2 MC02 enclosure: IP 55
Ambient air temperature Storage °F -40...176 (-40...80ºC)
Operation -4...140 (-20...60ºC)
Flame resistance Conforming to IEC 60695-2-1 °F 1760 (960ºC)
Maximum operating altitude ft 6561.68 (2000m)
Cabling
Number of conductors
and c.s.a.
Min. Max.
Solid cable mm
2
2 x 1 2 x 6
Flexible cable without cable end mm
2
2 x 1.5 2 x 6
Flexible cable with cable end mm
2
2 x 1 2 x 4
AWG 75ºC CU 8-18
Suitable for isolation Conforming to
IEC 60947-1 § 7-1-6
Yes
Tightening torque Lbf.in 15.05 (1.7N.m)
Rated operational voltage
(Ue)
Conforming to IEC 60947-2 V 690
Rated insulation voltage
(Ui)
Conforming to IEC 60947-2 V 690
Rated operational frequencyConforming to IEC 60947-2 Hz 50/60
Rated impulse withstand
voltage (U imp)
Conforming to IEC 60947-2 kV 6
Total power dissipated per
pole
W 2.5
Mechanical durability
(C.O.: closing, opening)
C.O. 100 000
Electrical durability For AC-3 duty C.O. 100 000
Duty class
(maximum operating rate)
C.O./h 25