Product Overview
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Apr 5, 2021
1
Product data sheet
Characteristics
DPE18G7
Easy TeSys DPE IEC contactor, 18 A, 3 P, 7.5
HP at 480 VAC, nonreversing, 120 V 50/60 Hz
coil
Main
Range Easy TeSys
Product name Easy TeSys DPE
Product or component
type
Contactor
Device short name DPE
Contactor application Resistive load
Motor control
Complementary
Utilisation category AC-4
AC-1
AC-3
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 18A (at <60°C) at <= 440 V AC AC-3 for power circuit
25A (at <60°C) at <= 440 V AC AC-1 for power circuit
Motor power kW 3KW 220...230 V AC 50/60 Hz
5.5KW at 380...400 V AC 50/60 Hz
5.5KW 415...440 V AC 50/60 Hz
7.5kW at 500 V AC 50/60 Hz
Maximum Horse Power Rating 0.5Hp 115 V AC 50/60 Hz 1 phase
2Hp 230/240 V AC 50/60 Hz 1 phase
3Hp 200/208 V AC 50/60 Hz 3 phase
3hp 230/240 V AC 50/60 Hz 3 phase
Control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 120 V AC 50/60 Hz
Auxiliary contact composition 1 NO
[Uimp] rated impulse withstand voltage 6kV conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 10A 140°F (60°C) signalling circuit
25A (at 60°C) for power circuit
Irms rated making capacity 250A at 440 V for power circuit conforming to IEC 60947
140A AC signalling circuit IEC 60947-5-1
250A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 250A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating 10A gG signalling circuit IEC 60947-5-1
40A gG at <= 690 V coordination type 1 for power circuit
25A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5mOhm - Ith 25A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit 690V IEC 60947-4-1
Power circuit: 600V CSA certified
Power circuit: 600V UL certified
Signalling circuit 690V IEC 60947-1
Electrical durability 1Mcycles 18A AC-3 <= 440 V
0.6Mcycles 25A AC-1 <= 440 V