Apr 5, 2021
1
Product data sheet
Characteristics
DPE18G7
Easy TeSys DPE IEC contactor, 18 A, 3 P, 7.5
HP at 480 VAC, nonreversing, 120 V 50/60 Hz
coil
Main
Range Easy TeSys
Product name Easy TeSys DPE
Product or component
type
Contactor
Device short name DPE
Contactor application Resistive load
Motor control
Complementary
Utilisation category AC-4
AC-1
AC-3
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 18A (at <60°C) at <= 440 V AC AC-3 for power circuit
25A (at <60°C) at <= 440 V AC AC-1 for power circuit
Motor power kW 3KW 220...230 V AC 50/60 Hz
5.5KW at 380...400 V AC 50/60 Hz
5.5KW 415...440 V AC 50/60 Hz
7.5kW at 500 V AC 50/60 Hz
Maximum Horse Power Rating 0.5Hp 115 V AC 50/60 Hz 1 phase
2Hp 230/240 V AC 50/60 Hz 1 phase
3Hp 200/208 V AC 50/60 Hz 3 phase
3hp 230/240 V AC 50/60 Hz 3 phase
Control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 120 V AC 50/60 Hz
Auxiliary contact composition 1 NO
[Uimp] rated impulse withstand voltage 6kV conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 10A 140°F (60°C) signalling circuit
25A (at 60°C) for power circuit
Irms rated making capacity 250A at 440 V for power circuit conforming to IEC 60947
140A AC signalling circuit IEC 60947-5-1
250A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 250A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating 10A gG signalling circuit IEC 60947-5-1
40A gG at <= 690 V coordination type 1 for power circuit
25A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5mOhm - Ith 25A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit 690V IEC 60947-4-1
Power circuit: 600V CSA certified
Power circuit: 600V UL certified
Signalling circuit 690V IEC 60947-1
Electrical durability 1Mcycles 18A AC-3 <= 440 V
0.6Mcycles 25A AC-1 <= 440 V

Summary of content (3 pages)