Product Overview

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jan 23, 2021
1
Product data sheet
Characteristics
DPE25BL
Easy Tesys DPE IEC contactor, 25 A,3 P, 10
HP at 480 VAC, nonreversing, 24 V DC coil
Main
Range Easy TeSys
Product name Easy TeSys DPE
Product or component
type
Contactor
Device short name DPE
Contactor application Resistive load
Motor control
Complementary
Utilisation category AC-4
AC-1
AC-3
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 25A (at <60°C) at <= 440 V AC AC-3 for power circuit
32A (at <60°C) at <= 440 V AC AC-1 for power circuit
Motor power kW 4KW at 220...230 V AC 50/60 Hz
7.5KW at 380...400 V AC 50/60 Hz
9KW at 415...440 V AC 50/60 Hz
10kW at 500 V AC 50/60 Hz
Maximum Horse Power Rating 1Hp at 115 V AC 50/60 Hz for 1 phase motors
3Hp 230/240 V AC 50/60 Hz 1 phase
5Hp at 200/208 V AC 50/60 Hz for 3 phases motors
5hp at 230/240 V AC 50/60 Hz for 3 phases motors
Control circuit type DC
[Uc] control circuit voltage 24 V DC
Auxiliary contact composition 1 NO
[Uimp] rated impulse withstand voltage 6kV IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 10A 140°F (60°C) signalling circuit
32A (at 60°C) for power circuit
Irms rated making capacity 140A AC signalling circuit IEC 60947-5-1
250A DC signalling circuit IEC 60947-5-1
300A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 300A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating 10A gG signalling circuit IEC 60947-5-1
50A gG at <= 690 V coordination type 1 for power circuit
35A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5mOhm - Ith 32A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit 690V IEC 60947-4-1
Power circuit 600V CSA
Power circuit 600V UL
Signalling circuit 690V IEC 60947-1
Electrical durability 1Mcycles 25A AC-3 <= 440 V
0.6Mcycles 32A AC-1 <= 440 V
Power dissipation per pole 2.5W AC-1
0.8W AC-3

Summary of content (3 pages)