Specifications

Figure 17, WMC 150D, 2-Pass Evaporator, 2-Pass Condenser See page for notes.) 28
330654401_2 Pass Evap Production Unit
“B”
20.4
(518.2)
42.7
(1084.6)
9.1 (231.1)
1.4 (35.5)
5.2 (132.1)
“C” 5.2 (132.1)
8.0 (203.2)
8.0 (203.2)
78.0
(1981.2)
35.0
(889.0)
4.0
(101.6)
26.5
(673.1)
8.0”
QTY. 2
6.0”
QTY. 2
01.13
QTY. 8
3.7 (93.9)
“A”
31.2
(792.5)
6.9
(175.3)
18.2
(462.3)
12.6
(320.0)
39.3
(998.2)
26.5
(673.1)
13.2 (335.3)
19.2 (487.7)
Evaporator
Condenser
Inlet
Outlet
Out
In
1.0” FPT
Relief Valves
Dimensions Inches (mm)
WMC Unit Evaporator Condenser
A B C
9 Foot Shells E2209 C2009 8.8 (223.5) 134.2 (3408.7) 100.1 (2542.5)
150D
12 Foot Shells E2212 C2012 43.7 (1109.9) 169.1 (4295.1) 134.9 (3426.5)
NOTES:
1. The dimension drawing above is for standard production units. Certain early
production units will have a different control panel arrangement and a greater height
dimension.
2. Left-hand connections shown. Right-hand connections are available for either vessel.
3. For either right-hand or left-hand evaporator connections, the inlet will be on the left
side looking at the head, and the connection outlet on the right side.
Right-hand
Evaporator
Connections
Outlet
Inlet
4. See Physical Data and Weights section for component and unit weights.
5. Allow three feet of service access on all four sides. Most codes require four feet
clearance in front of control and electrical panels. Allow sufficient overhead
clearance to remove compressor depending on site and rigging method-minimum of
four feet.
6. Allow the length of the tubes, plus two feet on one end, for tube removal. The last
two numbers in the vessel code is the tube length in feet. Appropriately placed doors
can accommodate tube removal through them.
7. Obtain current certified drawings from the local McQuay office for final layout.
30 optional marine water box dimensions.
8. See page
Catalog WMC-4 25