Condensate pump
The pump is factory-wired and piped
internally to the condensate drain pan.
The pump can move liquid a maximum of
18 m (60 ft), which may include a
maximum lift of 3.5 m (11.5 ft) at a flow
rate of 87 l/hr (23 gph). For example, if
your lift is 3 m (10 ft), you will have 15 m
(50 ft) of usable run remaining. The pump
uses an on-board condensate high level
float switch wired into the equipment for
alarm capabilities.
The condensate drain line can be
connected through either the top or the bottom of the equipment using factory-installed male
quick connectors and tubing approved by local building codes that will allow the drain line
connector to be moved approximately 25 mm (1 in.) away from the equipment. This facilitates
removing the equipment from a row. Female quick connectors and reduction fittings are
supplied with the equipment. Connect the fittings as shown, then connect the drain line quick
connector to the top or bottom condensate pump output line.
NOTE: Perform all piping in accordance with applicable industry guidelines as well as local and national codes
and regulations.
Condensate overflow.
Item Description
Tubing (field supplied and installed)
1/2-in. male NPT or 1/2-in. male BSPT fitting
(field supplied and installed)
Straight reduction (supplied)
Quick connector (supplied)
NOTICE
WATER DAMAGE
• Failure to properly route the condensate pump drain line before operation could result in
water damage.
• Do not route drain or supply lines above computer equipment, Uninterruptible Power
Supply (UPS) units, Power Distribution Units (PDUs), or light fixtures.
Failure to follow these instructions can result in equipment damage.
NOTICE
WATER DAMAGE
Failure to properly route condensate drain line before operation could result in water
damage.
Failure to follow these instructions can result in equipment damage.