Installation manual

41InRow RC Installation Manual
Bottom routing
1. Locate the supplied knockout plate.
2. Install the knockout plate on the top of the equipment where you removed the
power connection plate and power cords.
3. Locate the power connection plate in the bottom of the unit. See “Bottom piping
and power access locations (bottom view)” on page 20.
4. Loosen the screw securing the connection plate, and remove the plate.
5. Enlarge the two pilot holes in the connection plate as needed to accept conduit
connectors.
6. Attach the conduit connectors to the connection plate. Secure the connection plate
to the bottom of the equipment.
7. Route the cabling to the main breakers as shown.
8. Fasten the cabling inside the unit with the provided tie wraps.
9. Connect feed A and feed B power wiring to the tops of the two main circuit breakers
using the torque specified on the breakers. Connect the phases of the two power
feeds as marked next to the terminals.
10.Connect the ground wires to the ground terminal block located just above the main
circuit breakers.
11.Reinstall the connection plate and the electrical panel cover.
Strain relief (ACRC502 only)
1. Hook one strain relief into a pair of slots in each of the
two locations shown. See “Install kit inventory” on
page 8.
2. Route the electrical cable up from the bottom of the
equipment, passing through each strain relief.
3. Tighten the screw on each strain relief to capture the
electrical cable, taking the weight off of the inner
conductors.
4. Continue connecting electrical wiring to the circuit
breaker.
na2328a
na2542a