InRow RC Installation Manual42
Voltage selection
Your equipment can operate at various supply voltages, provided the proper
voltage jumpers are connected to the input transformers. Read the part number on
the jumpers connected at the factory and compare that number to the table below.
If the correct jumpers for your input voltage are not connected, remove them and
connect the proper jumper.
Jumper Connections
Transformer A connected to J50 (
)
SKU Input Voltage Use Jumper Part Number
ACRC500
208 (50/60 Hz) 0W2540 (default)
230 (50/60 Hz) 0W2541
ACRC501
460 (60 Hz) 0W2545
480 (60 Hz) 0W2546 (default)
ACRC502
380 (50/60 Hz) 0W2542
400 (50/60 Hz) 0W2543 (default)
415 (50/60 Hz) 0W2544