Specifications
Advanced Configuration Features
31004624 8/2009 109
Each block has a fixed number of registers reserved for its use. Whether or not all 
the registers reserved for that block are used in an application, the number of 
registers allocated to that block remains constant. This permits you to know at all 
times where to begin looking for the type of data of interest to you.
For example, to monitor the status of the I/O modules in the process image, look at 
the data in block 11 beginning at register 45392.
Reading Register Data
All the registers in the data image can be read by an HMI panel connected to the 
island at the NIM’s CFG port (see page 32). The Advantys configuration software 
reads all this data, and displays blocks 1, 2, 5, 8, 10, 11, and 12 in the Modbus Image 
screen in its I/O Image Overview.
Writing Register Data
Some registers, usually configured number of registers in block 12 (registers 
49488 through 49999) of the data image, may be written to by an HMI panel 
(see page 128).
The Advantys configuration software or an HMI panel may also be used to write data 
to the registers in block 1 (registers 40001 through 44096). The configuration 
software or the HMI panel must be the island bus master in order for it to write to the 
data image—i.e., the island must be in test mode.










